Field reference · standards & math
Backflow pass/fail calculator, and what ASSE 5110 actually covers
Two things get conflated constantly: the standard that says a tester is qualified, and the standards that say an assembly is built and performs correctly. This page separates them, then lets you run real readings through the same rule engine the BackflowPass generator uses.
Pass/fail calculator
Pick an assembly, type in what your gauge shows, and every reading is graded against the baseline thresholds — including the calculated buffer on the reduced pressure families. This is the shipped rule engine, not a marketing copy of it, so the verdict here is the verdict a report gets.
Passed on these readings
RP / RPZ · BackflowPass hydraulic baseline · all required readings recorded
4.8 PSID
Check #1 − relief opening · minimum 3.0 PSID
Reading by reading
- Check Valve #1Pass at 5.0 PSID or greater8.2 PSIDPass
- Differential Relief ValvePass at 2.0 PSID or greater opening point3.4 PSIDPass
- Buffer (Check #1 - Relief)Check #1 minus relief opening, 3.0 PSID or greater4.8 PSIDPass
- Check Valve #2Tight against backpressureTightPass
- Shutoff Valve #1Tight, no bypass leakageTightPass
- Shutoff Valve #2Tight, no bypass leakageTightPass
Grading readings is the fast part; the report is the rest of the job. Open the generator to attach these readings to a facility, an assembly serial number, repairs and retest, signatures and a one-page PDF.
Tester qualification versus assembly product standards
These are separate documents, written for separate audiences, and mixing them up leads to claims nobody can support — including software claiming to be "ASSE certified", which is not a thing that applies to a report generator.
| Tester qualification (ASSE Series 5000) | Assembly product standards | |
|---|---|---|
| What it describes | Tester qualification (ASSE Series 5000):What a person must know and demonstrate — for example a backflow prevention assembly tester under ASSE 5110. | Assembly product standards:How an assembly must be constructed and how it must perform, by assembly type. |
| Who it applies to | Tester qualification (ASSE Series 5000):The individual holding the certification. | Assembly product standards:The manufacturer's product, and by extension the assembly in the vault. |
| Where you meet it | Tester qualification (ASSE Series 5000):Certification and recertification, and the credential number on your reports. | Assembly product standards:Approved-assembly lists, submittals, and the model number on the tag. |
| What it does not do | Tester qualification (ASSE Series 5000):It does not set the pass/fail differentials you record in the field. | Assembly product standards:It does not qualify you to test, and it does not approve software. |
Where field pass/fail numbers actually come from
The minimum differentials a tester records against come from the field test procedure the authority having jurisdiction adopts — commonly drawn from USC Foundation and AWWA material, state program rules, and the manufacturer's instructions for that assembly. That is why two neighbouring purveyors can hand you procedures that differ in detail, and why software that hardcodes one set of numbers eventually gets someone in trouble.
Assembly product standards you will see referenced
| Assembly | Commonly cited product standard | What you test |
|---|---|---|
| RP / RPZ — reduced pressure principle | Commonly cited product standard:ASSE 1013 | What you test:Check #1, relief valve opening, calculated buffer, check #2 tight |
| DC / DCVA — double check valve | Commonly cited product standard:ASSE 1015 | What you test:Check #1 and check #2 differentials |
| PVB — pressure vacuum breaker | Commonly cited product standard:ASSE 1020 | What you test:Air inlet opening point, check valve holding |
| SVB — spill-resistant vacuum breaker | Commonly cited product standard:ASSE 1056 | What you test:Air inlet opening point, check valve holding |
| DCDA — double check detector assembly | Commonly cited product standard:Double check family plus bypass metering | What you test:Double check readings, plus the bypass assembly |
| RPDA — reduced pressure detector assembly | Commonly cited product standard:Reduced pressure family plus bypass metering | What you test:Reduced pressure readings, plus the bypass assembly |
Detector assemblies are not a third rule family: they inherit the parent family's procedure and add the bypass meter and bypass assembly to the paperwork. Field detail for each type lives on the RP/RPZ, DCVA and PVB reference pages.
The baseline thresholds in full
Every number the calculator and the generator use, in one place. These are read from the same constant the app runs on, so this table cannot drift out of date relative to the product.
| Family | Reading | Minimum |
|---|---|---|
| Reduced pressure (RP, RPDA) | Reading:Check valve #1 differential | Minimum:5.0 PSID |
| Reduced pressure (RP, RPDA) | Reading:Relief valve opening point | Minimum:2.0 PSID |
| Reduced pressure (RP, RPDA) | Reading:Buffer (check #1 − relief) | Minimum:3.0 PSID |
| Double check (DC, DCDA) | Reading:Check valve #1 differential | Minimum:1.0 PSID |
| Double check (DC, DCDA) | Reading:Check valve #2 differential | Minimum:1.0 PSID |
| Vacuum breaker (PVB, SVB) | Reading:Air inlet opening point | Minimum:1.0 PSID |
| Vacuum breaker (PVB, SVB) | Reading:Check valve holding | Minimum:1.0 PSID |
| All families | Reading:Shutoff valves #1 and #2 | Minimum:Must hold tight |
How the overall verdict is derived
The rules that matter as much as the numbers, because they are where reports usually go wrong:
- A missing reading is incomplete, not a failure. An unrecorded number is not evidence of a defect, and reporting it as one is not defensible.
- The overall result is derived, never selected. There is no control anywhere in the app that marks an assembly as passing; the status follows from the readings and the shutoff toggles.
- Failures carry structured reasons. Each failure has a code and a sentence stating what measured what against which minimum, so the report says why rather than just "failed".
- Displayed values round to one decimal; stored values do not. Rounding for display never changes the number the verdict was computed from.
- A retest does not erase the first test. The failed initial readings, the repairs and the final retest all persist, and a successful retest reports as passed after repair.
Questions testers actually ask
What is ASSE 5110?
ASSE 5110 sits in ASSE International's Series 5000 professional qualifications standards, which describe what a person must know and be able to do — in this case, a backflow prevention assembly tester. It is a standard about the tester, not about the assembly and not about the pass/fail numbers. Confirm the current edition and scope with ASSE directly, and confirm which qualification your state or purveyor actually accepts.
Then which standards cover the assemblies themselves?
Assembly product standards are a different series: ASSE 1013 for reduced pressure principle assemblies, 1015 for double check valve assemblies, 1020 for pressure vacuum breakers and 1056 for spill-resistant vacuum breakers. These describe how an assembly must be built and how it performs, and they are typically referenced alongside AWWA and USC Foundation material by the authority that approves assemblies for use.
Does this calculator certify my test?
No. It applies the same thresholds the BackflowPass generator applies, so you can see how a set of readings grades and where the margins are. Certification comes from a qualified tester signing a report that the receiving authority accepts. BackflowPass is not certified, approved or endorsed by ASSE International, the USC Foundation or any purveyor.
Why can the buffer be treated as advisory?
Buffer is check #1 differential minus the relief valve opening point on a reduced pressure principle assembly. Baseline practice here treats less than 3.0 PSID as a failure because a small margin means the relief is close to discharging in service. Some purveyors read it as informational instead. The rule engine exposes that as a switch so both verdicts are visible rather than hidden in the code.
Can the thresholds be changed for my jurisdiction?
Yes — every threshold lives in one rule set rather than being scattered through the app, and additional named rule sets can be registered. If your purveyor publishes different minimums, treat the shipped baseline as a starting point and configure it rather than working around it.
Related field references
RPZ test report form
What an RP/RPZ report has to contain, the field test order, the 5.0 / 2.0 / 3.0 PSID pass criteria and worked buffer math.
DCVA test sheet
Double check valve assembly test sheet: both check differentials, shutoff verification and how a DCDA fire line differs.
PVB inspection form
Pressure vacuum breaker test form: air inlet opening point, check holding, and the SVB differences worth knowing.
USC cross-connection reference
What the USC Foundation publishes, how approved-assembly lists work, and where to find your own jurisdiction's rules.
Fill this out on the phone instead.
The generator asks for exactly these fields, grades every differential as you type, opens repair and retest fields when something fails, and hands you the finished one-page PDF. No account, no install, works with no signal.